CZ HB ND DALI
Images shown are for illustration purposes only and may not be an exact representation of the productCZ HB ND DALI
High bay controls for DALI ballasts.
ControlZAPP can help you and your customers significantly reduce your energy bills. Whether specifier, building or estates manager, contractor or facilities manager ControlZAPP can control your lighting (or other connected loads) when and how is best suited for you at a very competitive price tag. ControlZAPP functionality with scheduling for DALI (broadcast) dimmable ballasts. High Bay mounting. Remotely adjusted using a free app on an Android phone or tablet. External DALI power supply unit (supplied). Additional Features - Accurate ‘Real time’ clock with battery back up when powered off - Accurately timed override ON or OFF - Active or Passive PIR occupancy switching - Patented ‘Intelligent’ photocell calibration - Automatic Daylight Savings Time (BST) correction with offset adjustment - Automatic Sunrise / Sunset prediction. This feature can be remotely adjusted via APP. - Upload indicator to ensure successful programming. - LED indicator for presence recognition within its detection range (can be turned off). - Manual Group Control ON / OFF / RESUME feature on APP
Detection Range
Up to 12m
Voltage
Suitable for mains voltage 100 - 260Vac, 50Hz (switch mode).
Loading
Suitable for switching and dimming DALI ballasts (broadcast only) and can control up to 40mA, eg. 20 ballasts at 2mA (varies according to make and model of ballasts). DANLERS DALI Power Supply Unit is rated at 40mA (DALI standard allows 250mA maximum). The controls interface of a DALI ballast normally sources at 2mA. Please refer to your ballast instructions. They can also switch up to: 10 amps (3000W) of resistive loads 6 amps (1500W) fluorescent lamps, high frequency or switch start, incandescent or mains halogen lamps (recommended with integral safety fuse) 3 amps (750W) of electronic or wire wound transformers. 2 amps (500W) of low energy lamps: CFL, LED drivers and LED lamps and fittings. 1 amp (250W) of fans or most metal halide lamps.
Minimum Load
2W resistive, suitable for most energy saving lamps, LED’s and emergency fittings.
Time Lag
Can be easily adjusted by APP to individual requirement from 10 seconds to 23 hours 59 minutes 59 seconds
Short Visit Time
Can be easily adjusted by APP to individual requirement from 10 seconds to 23 hours 59 minutes 59 seconds
Lux
Enabled: 30 to 1000 lux and infinite lux (photocell inactive).
Sensitivity
Adjustable via APP.
Output
Mains switching or DALI switching functionality.
Dimensions
Device: 90mm diameter x 63mm Power Supply: 120 x 50x 32mm