PIR occupancy switches with daylight linked dimming

cefl-main

CEFL PIR DALIP Installation Guide

CEFLA PIR DALIP Installation Guide

Ceiling flush-mounted PIR occupancy switches with closed loop control for DALI ballasts

CEFL PIR DALIP and CEFLA PIR DALIP can be used to control up to 12 high frequency DALI dimmable ballasts (broadcast). They incorporate a passive infra-red quad sensor to detect movement of a warm body within its detection zone and a photocell to monitor the ambient light level. The products can be flush mounted into suspended and plasterboard ceilings.

Product code: CEFL PIR DALIP and CEFLA PIR DALIP

 

CEFL PIR DALIP (Presence detection)

CEFL PIR DALIP operates by Presence Detection. The PIR switch will automatically switch the lights ON when a person enters the room. It will automatically switch the load OFF or to its reduced lux level (minimum) when no further movement is detected for its RUN-ON time.


CEFLA PIR DALIP (Absence detection - momentary switch required)

CEFLA PIR DALIP operates by Absence Detection. It requires a retractive (momentary) switch to be pressed when a person enters the room. This will switch the lights ON and enable the PIR switch to control the load. The load will automatically be switched OFF or to its reduced lux level (minimum) when no further movement is detected for its RUN-ON time.


Run-on timer - Step down illuminance

RUN-ON SET TO 0 SECONDS: When an area is no longer occupied the control will switch OFF from the maintained lux level after a pre-selected time lag (10 seconds to 40 minutes in 9 steps) if the RUN-ON timer is set a 0 seconds.

RUN-ON SET TO 1 MINUTE TO 30 MINUTES: When an area is no longer occupied the control will dim down to a minimum setting from the maintained lux level after a pre-selected time lag (10 seconds to 40 minutes in 9 steps) if the RUN-ON timer is set from 1-30 minutes.

The lights will stay ON at this reduced level for the pre-selected RUN-ON time then switch the lights OFF. If the PIR detects movement of a warm body while the RUN-ON is timing down the lights will switch ON to the maintained (maximum) lux level.

RUN-ON SET TO INFINITE: When an area is no longer occupied the control will dim down to a minimum setting from the maintained lux level after a pre-selected time lag (10 seconds to 40 minutes in 9 steps) if the RUN-ON timer is set at infinite.

The lights will stay ON at the reduced (minimum) lux level indefinitely until movement of a warm body is detected then the lights will switch ON at maximum and then to the maintained lux level.

Please note: Maximum and minimum levels could be set within the ballast NOT the DANLERS control.

 

Specification

Detection Zone: 360°
Time lag range: 10 seconds to 40 minutes in 9 steps
Run-on time: 0, 1, 2, 5, 10, 15, 20, 30 mins and infinite (always ON at minimum)
Photocell range: 30 to 1000 lux, and inactive
Loading: Daylight linked dimming with occupancy switching.
For controlling DALI dimmable ballasts (broadcast only).
These controls have an integral DALI Power Supply Unit suitable for use with up to 12 DALI ballasts, assuming each ballast has a constant current output of 1mA.
These controls can also switch up to 6 amps (1500W) of dimmable fluorescent lamps.
2 amps (500W) of CFL, LED Drivers and LED lamps and fittings.
Dimensions: 72mm diameter x 68mm

 

 

Daylight linked dimmer functions

 

pir-dld-function-1 pir-dld-function-1 pir-dld-function-1
UNOCCUPIED DAY -
LIGHTS OFF
(Timed or zero run-on)
OCCUPIED DAY -
LIGHTS ON (MAXIMUM)
(Maintained lux value)
UNOCCUPIED -
LIGHTS ON (MINIMUM)
(Timed or infinite run-on)
pir-dld-function-1 pir-dld-function-1
OCCUPIED NIGHT -
LIGHTS ON (MAXIMUM)
(Maintained lux value)
UNOCCUPIED NIGHT -
LIGHTS OFF
(Timed or zero run-on)

 

 

 

 

  • DimensionsOpen or Close
    Requires 63 or 64mm (2.5”) diameter hole in a false or plasterboard ceiling cefl-dimensions
  • Detection DiagramsOpen or Close

    icn-detection-strongStrong detection zone
    ie. person moving arm

    icn-detection-secondarySecondary detection zone
    ie. person walking (less sensitive when walking straight towards PIR switch)

    PIR Quad detector gives 124 detection areas within the zone

    cefl-detection-diagram-1

    Perspective view of detection zone

    For optimum coverage recommended mounting height between 2.4 and 5m

     

     

    Covering large areas

    To cover large areas it is advisable to install one CEFL PIR DALIP (or CEFLA PIR DALIP) to dim and a few CEFL PIR to switch

    cefl-detection-diagram-2
  • Wiring DiagramsOpen or Close
    CEFL PIR DALIP controlling several DALI dimmable ballasts cefl-pir-10vdc
    CEFLA PIR DALIP controlling several DALI dimmable ballasts cefla-pir-10vdc