High Bay PIR occupancy switches with Short visit / Exit Mode

High Bay Narrow

Narrow detection:
HB PIR ND SV

High Bay Spot

Spot detection:
HB PIR SP SV

High Bay Wide

Wide detection:
HB PIR WD SV

 

EasyZAPP

Download Installation Guide (not currently available)

This range of passive infra-red occupancy switches is designed for the automatic control of lighting loads with the additional benefit of manual temporary intervention when used with a retractive wall switch (momentary).
The controls are hard wired version and can be mounted directly onto solid ceilings or onto a range of different mounting boxes.

 

AUTOMATIC ONLY

The PIR switch will switch ON the connected load automatically when an area is occupied, and then switch it OFF automatically when the area has been vacant for a chosen duration (time lag). This has the benefits of reduced energy bills and automatic control. When being used to control lighting, the built-in photocell can be used to keep the lights off on bright days.

 

AUTOMATIC WITH MANUAL TEMPORARY INTERVENTION

When entering a room the retractive switch (momentary) is pressed activating a 30 second load ON time. If the person stays longer than 30 seconds within the zone of detection the load will then go into standard PIR switch functionality with its full time lag (adjustable from 10 seconds to 40 minutes). On leaving if the retractive switch is pressed the load will switch OFF after 30 seconds.

Specification

Detection zone: 360°
Run-on time:

0, 1, 2, 5, 10, 15, 20, 30 mins and infinite (always ON at minimum)

Minimum load: 2W resistive, suitable for most energy saving lamps, LED’s and emergency fittings.
Photocell range: 30 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive loads.
Up to 6 amps (1500W) of fluorescent loads.
Up to 3 amps (750W) of electronic and wire wound transformer loads.
Up to 2 amps (500W) of CFL, 2D lamps, LED Drivers and LED lamps and fittings.
Up to 1 amp (250W) of fans.
Dimensions: 90mm diameter x 63mm