High Bay PIR occupancy switches with Short visit / Exit Mode
Narrow detection: |
Spot detection: |
Wide detection: |
![]() |
This range of passive infra-red occupancy switches is designed for the automatic control of lighting loads with the additional benefit of manual temporary intervention when used with a retractive wall switch (momentary). |
AUTOMATIC ONLY
The PIR switch will switch ON the connected load automatically when an area is occupied, and then switch it OFF automatically when the area has been vacant for a chosen duration (time lag). This has the benefits of reduced energy bills and automatic control. When being used to control lighting, the built-in photocell can be used to keep the lights off on bright days.
AUTOMATIC WITH MANUAL TEMPORARY INTERVENTION
When entering a room the retractive switch (momentary) is pressed activating a 30 second load ON time. If the person stays longer than 30 seconds within the zone of detection the load will then go into standard PIR switch functionality with its full time lag (adjustable from 10 seconds to 40 minutes). On leaving if the retractive switch is pressed the load will switch OFF after 30 seconds.
Specification
Detection zone: | 360° |
Run-on time: |
0, 1, 2, 5, 10, 15, 20, 30 mins and infinite (always ON at minimum) |
Minimum load: | 2W resistive, suitable for most energy saving lamps, LED’s and emergency fittings. |
Photocell range: | 30 to 1000 lux, and inactive |
Loading: | Up to 6 amps (1500W) of resistive loads. Up to 6 amps (1500W) of fluorescent loads. Up to 3 amps (750W) of electronic and wire wound transformer loads. Up to 2 amps (500W) of CFL, 2D lamps, LED Drivers and LED lamps and fittings. Up to 1 amp (250W) of fans. |
Dimensions: | 90mm diameter x 63mm |
- DimensionsOpen or Close
Dimensions: 90 x 90 x 63 mm - Detection DiagramsOpen or Close
- Wiring DiagramsOpen or Close
Single HB PIR (xx) SV A few HB PIR (xx) SV wired in parallel - Batten Mount VariantsOpen or Close
Versions of the above controls are also available with batten mount fixings for mounting on the end of a lighting batten via the 20mm knock out. Complete with 1m tail leads.
Please contact us for further details. - Volt Free VariantsOpen or Close
Volt free variants
Versions of the above controls are also available with volt free contacts.